Date:04-27-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:1900868SYSTEM NAME:RIVERS END TRAILER PARKCOUNTY:LOS ANGELES 
SOURCE NO.:801SOURCE NAME:SAMPLING...*SOURCE CLASS:DBPASTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2943 BROMODICHLOROMETHANE 9.000 1.000 UG/L 1 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2942 BROMOFORM 12.000 1.000 UG/L 1 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2941 CHLOROFORM 4.000 1.000 UG/L 1 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2454 DIBROMOACETIC ACID 4.000 1.000 UG/L 1 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2944 DIBROMOCHLOROMETHANE 14.000 1.000 UG/L 1 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2451 DICHLOROACETIC ACID 3.000 1.000 UG/L 1 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2456 TOTAL HALOACETIC ACIDS (HAA5) 7.000 6.000 UG/L 60 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2453 MONOBROMOACETIC ACID < 1.000 UG/L 1 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2450 MONOCHLOROACETIC ACID < 2.000 UG/L 2 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2950 TTHM 39.000 4.000 UG/L 80 07-19-2023 12 2024/07
CA1900868_DST_801 DISINFECTION BYPRODUCTS-202407 2452 TRICHLOROACETIC ACID < 1.000 UG/L 1 07-19-2023 12 2024/07
CA1900868_DST_801 REGULATED SOC-null 2414 1,2,3-TRICHLOROPROPANE UG/L 0.005 3 DUE NOW
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

*Please refer to the Stage 2 DBP Monitoring Plan Approval Letter for full sample point names.
RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.